Operating thresholds
Hydrogen Sulfide (H₂S)
Parameter gas_h2s · ppm
| Band | Range |
|---|---|
normal | 0–10 ppm |
warning | 10–25 ppm |
danger | 25–45 ppm |
critical | ≥ 45 ppm |
Aligned with industrial hygiene practice for fixed-point detectors. Escape / ESD logic may trigger earlier based on wind and occupancy.
Process Temperature
Parameter temperature · °C
| Band | Range |
|---|---|
normal | 0–120 °C |
warning | 120–180 °C |
danger | 180–250 °C |
critical | ≥ 250 °C |
Generic process band; reactor bed and boiler steam circuits apply equipment-specific setpoints via DCS while SENTINEL uses this shared severity ladder.
Process Pressure
Parameter pressure · bar(g)
| Band | Range |
|---|---|
normal | 0–15 bar(g) |
warning | 15–28 bar(g) |
danger | 28–40 bar(g) |
critical | ≥ 40 bar(g) |
Covers intermediate hydrocarbon headers. LPG bullets and steam drums have PSV setpoints documented on equipment tags.
Worker Density
Parameter worker_presence · persons / zone
| Band | Range |
|---|---|
normal | 0–8 persons / zone |
warning | 8–15 persons / zone |
danger | 15–25 persons / zone |
critical | ≥ 25 persons / zone |
Simultaneous operations and turnaround crewing elevate density. Pair with permit status for confined-space work.
Ambient Noise
Parameter noise · dB(A)
| Band | Range |
|---|---|
normal | 0–85 dB(A) |
warning | 85–95 dB(A) |
danger | 95–105 dB(A) |
critical | ≥ 105 dB(A) |
Hearing conservation and escape-audibility thresholds for outdoor process areas.
Relative Humidity
Parameter humidity · % RH
| Band | Range |
|---|---|
normal | 20–70 % RH |
warning | 70–85 % RH |
danger | 85–95 % RH |
critical | ≥ 95 % RH |
High humidity affects electrostatic control at loading and corrosion rates on piping.
Critical Valve Deviation
Parameter valve_state · % open vs setpoint
| Band | Range |
|---|---|
normal | 0–5 % open vs setpoint |
warning | 5–15 % open vs setpoint |
danger | 15–30 % open vs setpoint |
critical | ≥ 30 % open vs setpoint |
Absolute deviation from expected ESD / process position. Stuck-open isolation on H₂S or LPG service is treated as critical.
Hazard catalog
Hydrogen Sulfide Release
Sour-service H₂S exposure risk from flanges, knockout drums, and vapor recovery. Immediately dangerous above occupational exposure limits; ignition risk when mixed with air in confined spaces.
Zones: zone-a-12zone-c-03
LPG BLEVE / Vapor Cloud
Pressurized LPG inventory can produce boiling liquid expanding vapor explosion (BLEVE) or dense vapor clouds if tank integrity or loading arms fail.
Zones: zone-d-05zone-e-09
High-Pressure Steam Jet
Superheated steam leaks from boiler headers and steam tracing can cause severe burns and force zone evacuation.
Zones: zone-b-07
Catalytic Runaway / Overpressure
Exothermic reaction excursions in the catalytic reactor train can drive rapid pressure and temperature rise requiring ESD.
Zones: zone-c-03
High-Pressure Hydrocarbon Line Break
Transfer headers between process units carry pressurized hydrocarbons; rupture creates jet fire and toxic dispersion pathways.
Zones: zone-a-12zone-b-07zone-c-03zone-d-05zone-e-09
Loading Arm Spillage / Vehicle Impact
Road tanker and rail rack operations introduce vehicle impact, hose disconnect, and static ignition hazards during product dispatch.
Zones: zone-e-09